The cool and hot water systems are closed or semi-closed ones. In these system, the recirculated water is not concentrated very much. But these system create conditions under which oxygen dissolved in water not easily liberated to the atmosphere. This often brings about corrosion of metals which leads to degradation of heat exchange efficiency, plugging of piping and other difficulties.
GREEN CX320 is a corrosion inhibitor designed to prevent these trouble in cool or hot water system.
<>
<>
Closed Cool/Hot Water System
<< Physical Properties >>
| CX 320 |
Appearance | Light yellow liquid |
pH * | 8.5 |
Specific gravity * | 1.1 |
Freezing point | <-10℃ |
*representative
<<Procedure for application>>
cleaning agent such as GREEN WX.
| Continuous Operation | Intermittent Operation |
Cool water system (mg/liter) | 400~800 | 2,000~4,000 |
Hot water system (mg/liter) | 1,000~2,500 | 3,000~5,000 |
range, replenish as necessary.
Cool water system (mg/liter) | 3,000~4,000 |
Hot water system (mg/liter) | 4,000~5,000 |
concentration of GREEN CX320 to 4,000 mg/liter or higher.
<<Package>> 20-kg polyethylene container
<<Handling Information>>
skin.