Cool and hot water systems are closed or semi-closed, in which the recirculating water is not concentrated so much, and dissolved oxygen is not easily released out of water into the atmosphere. These facts often cause corrosion of metals, which leads to the lowering of heat exchange efficiency, plugging of piping and other troubles.
GREEN CX360 is a corrosion inhibitor designed to prevent these troubles in cool or hot water systems.
<>
corrosion-inhibiting component
<>
Closed Cool/Hot Water System
<< Physical Properties >>
| CX 360 |
Appearance | Light yellow liquid |
pH * | 7.7 |
Specific gravity * | 1.15 |
Freezing point | <-5℃ |
*representative
<<Procedure for application>>
GREEN WX series.
dosage levels.
| Continuous Operation | Intermittent Operation |
Cool water system (mg/liter) | 500~1,000 | 2,000~3,000 |
Hot water system (mg/liter) | 1,500~2,500 | 3,000~4,000 |
(3)After dosing GREEN CX360, circulate the water for a few hours.
(4)Determine the concentration of GREEN CX360 in the system at least once a month. If the concentration becomes lower than the specified concentration range, supply the required quantity.
(5)When the system is shut down for an extended period of time, adjust the concentration of GREEN CX360 to 3,000 mg/L or higher.
<<Package>> 20-kg polyethylene container